Customization: | Available |
---|---|
Standard Component: | Standard Component |
Technics: | Assemble |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Description:
SensingInput Voltage 220/400VAC,1phase 2wire
Power Input Voltage 180~240VAC, 1phase 2wire
Output Voltage Max.90VDC@240VAC input
Current Continuous 6A
Intermittent 12A for 10SEE
Resistance Min.10Ω Max 100Ω
Voltage Build-up esidualvolts at AVR teminal>5VAC
External Volts Adjustment +/-7%with 1KΩ 1watt trimmer
Unit Power Dissipation Max.8Watt
Under Frequency Protection 60Hz system presets knee point at 57Hz
(Factory Settings) 50Hz system presets knee point at 47Hz
Technical Data:
Sensinginput |
Voltage |
220/400VAC,1 phase 2wire |
VoltageBuild-up |
Residualvolts at AVR teminal>5VAC |
Power Input |
Voltage |
180-240VAC,1 phase2wire |
External Vdits Adjustment |
±7%with 1k Ω1wait trimmer |
Output |
Voltage |
Max.90VDC@240V ACinput |
Sotf Start Ramp Time |
3sec. |
Current |
Continuous 6A |
Unit Power Dissipation |
Max.8Watt |
|
Intermittent 12A for 10SEE |
EMI Suppression |
Intermal Electromagnetic Interference Filtering |
||
Resistance |
Min.10Ω Max.100Ω |
Thermal.Drift |
0.05%per°C chage in AVR ambient |
|
Under Frequency Protection |
60Hzsystem presets knee pointat 57Hz |
|||
(Factory Settings) |
50Hzsystem presets knee point at 47Hz |
|||
Volts |
Regulation<±0.5%(with 4%engine goveming) |